Product - Fibershield-H

Fibershield®-H

The horizontal textile fire protection curtain for ceiling openings

Product description

The textile horizontal fire protection curtain for ceiling openings

Even large ceiling openings that required a wide area closure with extensive drop length can be optimally protected against the effects of fire with the Fibershield-H fire protection curtain. The system is characterised by its versatile mounting possibilities (below the ceiling, in the embrasure) and by its construction design. In the event of alarm, the system reliably closes by means of spring force without requiring an external power source.

Fibershield-H

Type

Textile fire protection curtain

Fabric

Protex 1100-B1 • Protex 1100.1 A2

Verification

UB III/B-08-016 • UB III/B-05-020

Closing direction

from left to right • from right to left

Fire resistance

E 120

Closing cycles

C

Constructive system design - System drawing

1 Smoke detector 2 Casing 3 Side guide 4 Fabric 5 Closing element 6 Tubular motor 7 Control module 8 Control with operating unit 9 Manual release


1 Smoke detector 2 Casing 3 Side guide 4 Fabric 5 Closing element 6 Tubular motor 7 Control module 8 Control with operating unit 9 Manual release

System

LB (m)

LH (m)

a (mm)

b (mm)

e (mm)

t (mm)

h (mm)

Gas spring

< 1.4

< 1.5

120

190

109

190

200

Gas spring

< 4.5

< 2.9

120

190

109

190

190

Gas spring

< 4.5

≥ 2.9 < 5

150

235

109

235

290

Gas spring

≥ 4.5 < 30

≥ 2.9 < 5

150

235

225

235

320

Duplex

< 20

≥ 2.9 < 8,5

160

80

355

274

355

Casing installation options

In ceiling embrasure

Below the ceiling