Product -

Fibershield®-I

System: Fibershield® | Series: Fibershield®-I

Product description

In case of alarm self-closing, thermally insulating

fire protection closure of textile construction in vertical installation position and closing direction.

Type

Heat-insulating fire protection closure with textile design

Verification

CE identification pursuant to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016

Closing direction

From top to bottom

Fire resistance

EI1 30 - EI2 120 • tested according to EN 1634-1: 2014-03 • Classified according to EN 13501-2:2016

Smoke protection

Classified according to EN 13501-2:2016

Closing cycles

C • C1 • C2 • tested according to EN 12605 : 2000-08 • Classified according to EN 13501-2:2016

Fire behaviour of textile

B-s1, d0; E-d2 • Tested according to ISO 11925-2 and EN 13823 • Classified according to EN 13501- 1:2018

Environmental conditions

Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.).

Visible surfaces

coated in RAL, NCS standard colour, stainless steel V2A material A-1.3401

Constructive system design - System drawing

1 Smoke detector 2 Housing 3 Guide rails 4 Attachment bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release


1 Smoke detector 2 Housing 3 Guide rails 4 Attachment bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release

Classification

Size max. [LB x LH] in mm

Wall thickness*

Housing

Guide rail [a (+c) x b]

EI130

7315 x 4950

150 mm

Type A or Type B

Type 1 or Type 3**

EI230

7315 x 4950

150 mm

Type A or Type B

Type 1 or Type 3**

EI160

6600 x 4840

150 mm

Type B

Type 2

EI260

6600 x 4840

150 mm

Type A or Type B

Type 1 or Type 3**

EI190

6000 x 4400

150 mm

Type B

Type 2

EI290

6000 x 4400

150 mm

Type B

Type 1

EI2120

6600 x 4840

175 mm

Type B

Type 2

C2

6600 x 4840

Sa

Joint length 14.5 m
(3-sided without
end strip)

* The wall can be low density (aerated concrete block) or high density (masonry or concrete). ** Type 3 guide rails – maximum size 3000 x 2870 mm

Casing installation options

Wall mounting with cover

Wall mounting suspended ceiling without cover

Wall without housing cover

Guide rails

Standard

Type 1

Type 2

Type 3