Product - Fibershield-S

Fibershield®-S

The space creating textile fire protection curtain that leads around the corner

Product description

Fire protection that leads around corners: The floor space of the closure can be realised in a rectangular and polygon-shape with angles between 30° and 150°. No support elements are required despite the corner design. In addition to a closed polygon shape, open systems can also be realised that close against the wall by installing special guide rails. The fire protection curtain can be closed without any external energy by means of the 'Gravigen' drive system that is included as standard. The Fibershield-S complex allows for complex sealing geometries to be realised, while also complying with the requirement of closing off a space for more than 90 minutes.

Fibershield-S

Type

Textile fire protection curtain

Achievable protection goals

EI - with fire load free zone • EW 90 • EI - with sprinklers

Fabric

Ecotex 1100 A2 • Heliotex

Fire load free zone

Protex/Ecotex: EI 30/60/90min 100/150/200 cm • Heliotex: EI 30/60/90min 20/30/50 cm

Verification

IBS 08062416 • UL 10 (b) (2009) • UL 10 (c) (2009) • UL 10 (d) (2009) • NFPA 252 (2012)

Closing direction

From top to bottom

Closing cycles

C1

Constructive system design - System drawing

1 Smoke detector 2 Casing 3 Side guids 4 Tubular motor 5 Fabric 6 Closing element 7 Coil 8 Control module 9 Control with operating unit 10 Manual release SL System length


1 Smoke detector 2 Casing 3 Side guids 4 Tubular motor 5 Fabric 6 Closing element 7 Coil 8 Control module 9 Control with operating unit 10 Manual release SL System length

Fabric

System width

Drop length (AL)

t

h

Ecotex 1100 A2

< 50 m

< 3 m

490 mm

125 mm

Ecotex 1100 A2

< 50 m

> 3 m - ≤6 m

490 mm

225 mm

Heliotex EW 90

< 50 m

< 2.2 m

490 mm

125 mm

Heliotex EW 90

< 50 m

> 2.2 m - ≤2.5 m

490 mm

225 mm

Heliotex EW 90

< 50 m

> 4.5 m - ≤6 m

490 mm

450 mm

Closing strips

Standard

Standard

Special

With light spots or light strip

Casing

Standard

Casing (open)

Casing - Casing (open)

h from table d 290 mm t 490 mm

Casing (closed)

Casing - Casing (closed)

h from table d 290 mm t 490 mm

Special

Casing EI (open)

 - Casing EI (open)

h 240 mm d 560 mm t 600 mm

Casing EI (closed)

 - Casing EI (closed)

h 240 mm d 560 mm t 600 mm

Locking equipment (optional)

 - Locking equipment (optional)

h 125 mm d 290 mm t 490 mm S Infrarot Sicherung

Guide rails

Standard

Guide for open polygons

Guide rails - Guide for open polygons

a 117 mm b 278 mm

References

Product - Segeberger Clinics

Segeberger Clinics