Produkt - Moducoil

Stoebich Smoke Curtain M

Product Description

Prefabricated single modules are linked into a complete smoke protection curtain unit in any length. Standard unrolled lengths up to 275.59" Designd for time class and temperature loads D = 1,112°F. As standard with a 'Gravigen' drive sytsem, i.e. closes without external power source, fire-resistant cables are not necessary. Durable drive systems suitable for high cycle numbers up to 10,000 cycles with approved brakes. Module-like assembly of the winding casing above or next to each other. Connected closure strip above all modules. Can be combined with sping-loaded closure strip. Also suitable (approved) as a floor-closing smoke curtain. Optionally with integrated passage doors in floor-closing curtains. Alternatively with lateral guide rails.

Moducoil

construction type

textile smoke curtain

proof

- Z - 56. 429 - 916

closing direction

from top to bottom

classifications according to DIN EN 12101-1

Klassifizierung nach DIN EN 12101-1

Constructive structure - Einzelmodul

1 Rauchmelder 2 Gehäuse 3 Textil 4 Abschlussleiste 5 Wickel mit Rohrmotor 6 Ansteuerungsmodul 7 Steuerung mit Bedieneinheit 8 Handauslöser


1 Rauchmelder 2 Gehäuse 3 Textil 4 Abschlussleiste 5 Wickel mit Rohrmotor 6 Ansteuerungsmodul 7 Steuerung mit Bedieneinheit 8 Handauslöser

system width (SB)

drop length (AL)

t

h

≤ 5 m

≤ 4,5 m

150 mm

150 mm

≤ 5 m

> 4,5 m - ≤ 7 m

185 mm

185 mm

> 5 m - ≤ 7 m

≤ 4,5 m

185 mm

185 mm

Constructive structure - Multi-module, above each other)

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

system width (SB)

drop length (AL)

t

h

> 7 m

4,5 m

160 mm

280 mm

> 7 m

4,5 m - ≤ 7 m

195 mm

350 mm

Constructive structure - Multi-module, next to each other)

1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release


1 Smoke detector 2 Casing 3 Fabric 4 Closing element 5 Tubular motor 6 Control module 7 Control with operating unit 8 Manual release

system width (SB)

drop length (AL)

t

h

> 7 m

4,5 m

250 mm

150 mm

> 7 m

4,5 m - ≤ 7 m

320 mm

185 mm

side guides

Wand

a 80 mm b 70 mm

Laibung

a 80 mm b 70 mm

Niesche

a 80 mm b 70 mm aN 85 mm bN 80 mm

housing

Standard

Single smoke protection (wall)

Single smoke protection (ceiling)

Modular smoke protection (wall/above one another)

Modular smoke protection (ceiling/above one another)

Modular smoke protection (ceiling/next to each other)

Modular smoke protection (wall/next to each other)

alternatives for installation

installation to the wall

installation to the ceiling

installation over suspension