Type | Textile smoke apron |
Proof of usability | CE according to DIN EN 12101-1 | UL 1784 |
Fabric | Protex 600.1 A2 | Protex 1100.1 A2 |
Verification | 0761-CPD-0060 |
Closing direction | From top to bottom |
Closing cycles | 1,000 cycles according to DIN EN 12101-1 |
Classification | DH 120 | D 60 | Classification according to DIN EN 12101-1 |
Triggering | Approved hold-open system | To be provided on site |
Constructive system design (with guide rail)
Legend System components:
1 = Smoke detector
2 = Casing
3 = Side guide
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release
11 = Wicket door (optional)
Fabric | System widt h(SB) | Drop length (AL) | t (mm) | h (mm) |
Protex 600.1 A2 / 1100.1 A2 | ≥ 0,8 m - ≤ 1,6 m | ≤ 3,5 m | 190 | 250 |
Protex 600.1 A2 / 1100.1 A2 | ≥ 1,6 m - ≤ 30 m | ≤ 3,5 m | 190 | 200 |
Protex 600.1 A2 / 1100.1 A2 | ≥ 1,2 m - ≤ 30 m | > 3,5 m - ≤ 6 m | 190 | 250 |
Protex 1100.1 A2 | ≥ 2,0 m - ≤ 20 m | > 6 m - ≤ 9 m | 235 | 290 |
Constructive system design (without guide rail)
Legend System components:
1 = Smoke detector
2 = Casing
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release
Fabric | System width (SB) | Drop length (AL) | t (mm) | h (mm) |
Protex 600.1 A2 / 1100.1 A2 | ≥ 0,8 m - ≤ 1,6 m | ≤ 3,5 m | 190 | 250 |
Protex 600.1 A2 / 1100.1 A2 | ≥ 1,6 m - ≤ 50 m | ≤ 3,5 m | 190 | 200 |
Protex 600.1 A2 / 1100.1 A2 | ≥ 1,2 m - ≤ 50 m | > 3,5 m - ≤ 6 m | 190 | 250 |
Protex 1100.1 A2 | ≥ 2,0 m - ≤ 50 m | > 6 m - ≤ 9 m | 235 | 290 |
Closing strips

Standard
Typ 4,6

Spring-loaded closing strip
Typ = 3,84 F (Special)

Spring-loaded closing strip
Typ = 4,6 F (Special)
Casing installation options

Wall mounting

Suspension mounting

Ceiling mounting
Guide rails

Type 105 E (niche)
a = 105 mm
b = 74 mm
AL = ≤ 6 m
A = ≤ 50 m²

Type 105 E (embrasure)
a = 105 mm
b = 74 mm
AL = ≤ 6 m
A = ≤ 50 m²

Type 105 E (Wall)
a = 105 mm
b = 74 mm
AL = ≤ 6 m
A = ≤ 50 m²

Type 80 E
a = 80 mm
b = 74 mm
AL = ≤ 3,5 m
A = ≤ 18 m²

Type 160 E
a = 160 mm
b = 100 mm
AL = ≤ 9 m
A = ≤ 120 m²