SUPERCOIL

Supercoil

Product description

Supercoil is outstanding for its flexibility in the implementation of made-to-measure solutions. The smoke apron consists of one web part up to 50 m in width and features a drop length of 9.5 m. It is designed for high time classes at temperature loads up to 600 0C (D) and 1,100°C (ETK curve - DH). If guide rails are used, the smoke apron ensures that zero smoke escapes over the entire width of the apron. Thanks to the 'Gravigen' drive motor the apron closes without external energy. Supercoil is also suitable as a floor-closing and partition-forming smoke apron and can be equipped with an opening that allows persons to pass. Furthermore, the clever design allows for a combination with the passable Stripecoil smoke apron.

TypeTextile smoke apron
Proof of usabilityCE according to DIN EN 12101-1 | UL 1784
FabricProtex 600.1 A2 | Protex 1100.1 A2
VerificationZ - 56. 429 - 916 | 0761-CPD-0060
Closing directionFrom top to bottom
Closing cycles1,000 cycles according to DIN EN 12101-1
ClassificationDH 120 | D 60 | Classification according to DIN EN 12101-1
TriggeringApproved hold-open system | To be provided on site

Constructive system design (with guide rail)

Supercoil

Legend System components:
1 = Smoke detector
2 = Casing
3 = Side guide
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release
11 = Wicket door (optional)

FabricSystem widt h(SB)Drop length (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 30 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 30 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 20 m> 6 m - ≤ 9 m235290

Constructive system design (without guide rail)

Supercoil

Legend System components:
1 = Smoke detector
2 = Casing
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release

FabricSystem width (SB)Drop length (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 50 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 50 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 50 m> 6 m - ≤ 9 m235290

Closing strips


Closing strips Fibershield-P
Standard
Typ 4,6
Closing strips Fibershield-P
Spring-loaded closing strip
Typ = 3,84 F (Special)
Closing strips Fibershield-P
Spring-loaded closing strip
Typ = 4,6 F (Special)

Casing installation options


Wall mounting
Wall mounting
Suspension mounting
Suspension mounting
Ceiling mounting
Ceiling mounting

Guide rails


Typ 105 E (niche)
Type 105 E (niche)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (embrasure)
Type 105 E (embrasure)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (Wall)
Type 105 E (Wall)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²


Typ 80 E
Type 80 E
a = 80 mm
b = 74 mm

AL = ≤ 3,5 m
A = ≤ 18 m²
Typ 160 E
Type 160 E
a = 160 mm
b = 100 mm

AL = ≤ 9 m
A = ≤ 120 m²