• US
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • Theme worlds
  • News
  • Contact
  • STÖBICH Brandschutz: Austria Contact

Stoebich Fire Curtain F

(Kopie 1)

  • Fibershield-F

Product description

The textile fire protection closure for openings in façades for installation outside buildings.

Efficient long-term and weather-resistant fire protection: Fire Curtain F is made of components that are tried and tested for outdoor use and offer many options for attachment to a wide variety of façades (with or without thermal insulation, with combustible or non-combustible insulation).

Drive and guide rails are heated regardless of the ambient temperature to ensure that, in the event of low temperatures, the gravity-fail-safe function works and that the lateral guide rails do not ice up.

Construction TypeTextile fire protection curtain
executable protection targetEW 90
FabricProtex 1100 2S | Heliotex
Fire load free zoneStoebich Fire & Smoke Fabric P 1100 2S | Stoebich Fire & Smoke Fabric H
ProofGU IV/97-73 | UB III/B-08-012 | B 15045 | UB III/B-05-006-A1
Closing directionFrom top to bottom
Fire resistanceE 30 | E 60 | E 90 | E 120 | EW 30 | EW 60 | 2 hours fire rating according to EN 1634-1
Closing cycles 10,000 cycles (drive unit)
Feasible size(F) fabric dependent Stoebich Fire & Smoke Fabric E: 5 x 2 m / 5 x 6 m (w x h) | fabric dependent Stoebich Fire & Smoke Fabric P: 5 x 6 m / 6 x 7 m (w x h)
Guide typeSide guides
BearingFixed bearing
Re-openingGravity-Fail-Safe | self-closing
Stoebich Fire Curtain F

Structural system design (system drawing)

FabricSystem width (SB)Drop length (AL)t (mm)h (mm)
Heliotex EW≥ 0,8m - ≤ 5 m≤ 2 m190250
Heliotex EW≥ 0,8m - ≤ 5 m≤ 5 m235290
Ecotex 1100 2S≥ 0,8m - ≤ 1,6 m< 3,5 m190250
Ecotex 1100 2S≥ 1,6m - ≤ 5 m< 3,5 m190200
Ecotex 1100 2S≥ 0,8m - ≤ 5 m> 3,5 m - ≤ 5 m190250

Bottom bar


Closing strips Fibershield-F
Heavy
Type 9,6
Closing strips Fibershield-F
Standard
Type 4,6
Closing strips Fibershield-F
Narrow
Type 5,61


Closing strips Fibershield-F
With window sill
Closing strips Fibershield-F
Standard

Bottom bar special


Closing strips Fibershield-F
Type 4,6 K
Closing strips Fibershield-F
Spring-loaded closing strip
Type 3,84 (Sonder)
Closing strips Fibershield-F
Type 3,84 FK

Alternatives for installation


Casing installation options Fibershield-F
Installation of the casing to the wall without insulation
Casing installation options Fibershield-F
Installation of the casing to the wall, with combustible insulation
Casing installation options Fibershield-F
Installation of the casing to the wall, with non-combustible insulation

Side guides


Guide rails Fibershield-F
With non-combustible heat insulation
Guide rails Fibershield-F
Without heat insulation
Guide rails Fibershield-F
With combustible heat insulation