Stoebich Smoke Curtain T
Oops, an error occurred! Code: 202504190924111aa0b74b
Type | Smoke protection closure of textile construction or non-thermally insulating fire and smoke protection closure |
Verification | CE identification pursuant to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016 |
Closing direction | From top to bottom |
Fire resistance | E 0 – EW 120 | tested in compliance with EN 1634-1:2014+A1:2018 | Classified according to EN 13501-2:2016 |
Smoke protection | Sa, S200 | tested in compliance with EN 1634-3:2005-01 | classified according to EN 13501-2:2016 |
Closing cycles | C, C1, C2 | tested in compliance with EN 12605:2000-08 and EN 12604:2017-12 | classified according to EN 13501-2:2016 |
Fire behaviour of the fabric | A2-s1, d0; B-s1, d0; E-d2 | tested in compliance with ISO 1716 and EN 13823 or ISO 11295-2 | classified according to EN 13501-1:2018 |
Environment conditions | Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.) |
Visible surfaces | galvanized, RAL - smooth - silk gloss - standard shade, NCS - standard shade |
Legendary system components:
1 = Smoke detector
2 = Housing
3 = Guide rail
4 = Control module
5 = Release device (Details of the electrical components are to be taken from the valid general type approval of the hold-open system.)
Legal dimensioning:
Structure
B = Clear shell construction height
A = Clear shell construction width
System
AY = System height
LH = Clear system height
LB = Clear system width
BJ = System width
Housing
BX = Depth
BW = Height
v = Offset between guide rail and housing
Guide rail
CD = Width
CE = Depth
BD = Offset left
BE = Offset right
Structural system design (system drawing)
Fabric | System width | Unrolled length t | t (mm) | h (mm) |
Stoebich Fire & Smoke Fabric P / E | < 32.8' | < 19.7' | 13.78'' | 10.24'' |
Stoebich Fire & Smoke Fabric P / E | < 16.4' | < 14.8' | 11.22'' | 7.87'' |
Stoebich Fire & Smoke Fabric P / E | < 11.5' | < 11.5' | 7.48'' | 11.41'' |
Stoebich Fire & Smoke Fabric P / E | < 23' | < 16.4' | 11.41'' | 14.17'' |
Stoebich Fire & Smoke Fabric E | < 23' | < 10.5' | 13.78'' | 10.24'' |
Stoebich Fire & Smoke Fabric E | < 16.4' | < 8.2' | 11.22'' | 7.87'' |
Stoebich Fire & Smoke Fabric E | < 11.5' | < 6.6' | 7.48'' | 11.41'' |
Stoebich Fire & Smoke Fabric E | < 19.7' | < 9.8' | 11.41'' | 14.17'' |
Housing

Ceiling mounting
Typ A: BX = 285 mm, BW = 200 mm
Typ B: BX = 350 mm, BW = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm

Wall mounting
Typ B: BX = 350 mm, BW = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm

Wall mounting suspended ceiling with cover
Typ B: BX = 350 mm, BW = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm
Guide rails

Type 1 (Wall mounting)
CD = 104 mm
CE = 74 mm
BD/BE ≥ 0 mm
v = 0 mm

Type 2 (Embrasure mounting)
CD = 104 mm
CE = 74 mm
v = 0 mm

Type 2 (Niche mounting)
CD = 104 mm
CE = 74 mm
v = 0 mm
CDN = 120 mm
CEN = 100 mm
Note: Dotted line for the winding shaft receptacle (housing)