      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • Theme worlds
  • News
  • Contact

Stoebich Fire & Smoke Curtain HC

(Kopie 1)

  • Fibershield-HC

Product description

In the event of an alarm, a room-enclosing or radiation-reducing textile fire protection closure that closes by means of an electric motor in a horizontal installation position and closing direction.

TypeRadiation-reducing, room-enclosing fire protection closure of textile design
VerificationCE marking according to hEN 16034 : 2014 in conjunction with hEN 13241 : 2003+A2 : 2016
Closing directionhorizontal
Fire resistanceE 120 | EW 90 | tested according to EN 1634-1 : 2014-03 | classified according to EN 13501-2 : 2016-12
Closing cyclesC, C1 | tested according to EN 12605 : 2000-08 | classified according to EN 13501-2 : 2016-12
DurabilityC:     for 2-part systems up to size 9400 x 18800 mm for E 120 and EW 60 or 6800 x 4270 mm for EW 90
C1:   for 1-part systems up to size 5000 x 5000 mm for EW 60 or 6000 x 6500 mm for E 120 and EW 30
Environmental conditionsIn the event of a fire, the falling of ceiling parts in the area of the the area of the soffit by suitable on-site measures on the part of the customer. Not taken into account are special environmental conditions (for example Humidity >80%, ambient | Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.)
Stoebich Fire & Smoke Curtain HC

Legend System components:
1 = Smoke detector
2 = Housing
3 = Guide rails
4 = Textile
5 = End element
6 = Tubular motor
7 = Control module
8 = Control with operating unit
9 = Manual release

Structural system design (system drawing)

ClassificationSize** [y x r] in mmTypeFabricWall Thickness* in mmHousing (t x h) in mmGuide Rail in mm
E 1206000 x 65001-tlgHeliotex 120300235 x 320200 x 80
EW 306000 x 65001-tlgHeliotex 120300235 x 320200 x 80
EW 605000 x 50001-tlgHeliotex 120300235 x 320200 x 80
E 1209400 x 188002-tlgHeliotex 120300400 x 610300 x 150
EW 609400 x 188002-tlgHeliotex 120300400 x 610300 x 150
EW 906800 x 42702-tlgHeliotex 120300400 x 610300 x 150

Alternatives for installation


nstallation of the casing to the wall, thermomechanically
Installation of the casing to the wall, thermomechanically

Housing


Housing Stoebich Fire & Smoke Curtain HC
Open state
Housing Stoebich Fire & Smoke Curtain HC
Closed state

Side Guides


Side Guides Stoebich Fire & Smoke Curtain HC
FS-HC directly under the ceiling