Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.
Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.
A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.
In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.
The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.
Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.
In the event of an alarm, self-closing, non-thermally insulating fire protection curtain in vertical installation position and closing direction with architectural requirements for housing and guide rails.
Construction type
Textile fire protection curtain
Fabric
Stoebich Fire & Smoke Fabric H | Fire & Smoke Fabric P
Fire load free zone
Meet backface temperature 250°F with sprinkler as compensation
Key: System components: 1 = Smoke detector 2 = Housing 3 = Guide rail 4 = Control module 5 = Release device (see the valid general type approval of the brake
system for design details of the electrical components.)
Key: Dimensions Structure B = Clear shell construction height A = Clear shell construction width System AY = System height LH = Clear system height LB = Clear system width BJ = System width Housing BX = Depth BW = Height v = Offset between housing and guide rail Guide rail CD = Width CE = Depth BD = Offset left BE = Offset right
Size dimensions and system structure
Fabric
System width (SB)
Unrolled length (AL)
t
h
Stoebich Fire & Smoke Fabric H
≥ 2.6' - ≤ 32.8'
≤ 6.6'
7.48''
9.84''
Stoebich Fire & Smoke Fabric H
≥ 2.6' - ≤ 32.8'
≤ 19.7'
9.25''
11.41''
Stoebich Fire & Smoke Fabric P
≥ 2.6' - ≤ 5.3'
≤ 11.5'
7.48''
9.84''
Stoebich Fire & Smoke Fabric P
≥ 5.3' - ≤ 32.8'
≤ 11.5'
7.48''
7.87''
Stoebich Fire & Smoke Fabric P
≥ 2.6' - ≤ 32.8'
≥ 11.5' - ≤ 19.7'
7.48''
9.84''
Stoebich Fire & Smoke Fabric P
≥ 2.6' - ≤ 32.8'
≥ 19.7' - 24.9'
9.25''
11.41''
Special sizes on request - technically feasible up to dimensions 22 x 9m (Protex 1100.1 A2) or 12 x 6 m (Heliotex) Stoebich Fire & Smoke
Winding housing
Ceiling mounting Typ A: BX = 190 mm, BW = 200 mm Typ B: BX = 190 mm, BW = 250 mm Typ C: BX = 235 mm, BW = 295 mm Typ D: BX = 270 mm, BW = 320 mm Typ E: BX = 300 mm, BW = 340 mm
Wall mounting Typ A: BX = 190 mm, BW = 200 mm Typ B: BX = 190 mm, BW = 250 mm Typ C: BX = 235 mm, BW = 295 mm Typ D: BX = 270 mm, BW = 320 mm Typ E: BX = 300 mm, BW = 340 mm
Ceiling installation suspended ceiling Typ A: BX = 190 mm, BW = 200 mm Typ B: BX = 190 mm, BW = 250 mm Typ C: BX = 235 mm, BW = 295 mm Typ D: BX = 270 mm, BW = 320 mm Typ E: BX = 300 mm, BW = 340 mm
Guide rails
Wall mounting Typ 1: CD = 80 mm | CE = 74 mm Typ 2: CD = 105 mm | CE = 74 mm Typ 3: CD = 160 mm | CE = 100 mm
BD/BE ≥ 0 mm v = 0 mm
Soffit mounting Typ 1: CD = 80 mm | CE = 74 mm Typ 2: CD = 105 mm | CE = 74 mm Typ 3: CD = 160 mm | CE = 100 mm
v = 0 mm
Recess mounting Typ 1: CD = 80 mm | CE = 74 mm Typ 2: CD = 105 mm | CE = 74 mm Typ 3: CD = 160 mm | CE = 100 mm