• EN
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • Theme worlds
  • News
  • Contact
  • STÖBICH Brandschutz: Austria Contact
Product - Fibershield-E

Fibershield®-E

The economical textile fire protection curtain with the highest degree of standardisation

Product description

High degree of standardisation and thus economical shielding system with "Gravigen" drive system, i.e. closing without external energy, so that no fire-resistant cables are required.

10.000 motor cycles are possible. Different classifications achievable through different fabric types. Large fire protection curtain systems at least class C 2.

Equipment options: Safety contact strip, spring-loaded closing strip

Fibershield-E

Type

Textile fire protection curtain

Achievable protection goals

EI - with fire load free zone • EI - with sprinklers

Fabric

Heliotex • Ecotex 1100 A2

Fire load free zone

Heliotex: EI 30/60/90min 20/30/50 cm • Protex/Ecotex: EI 30/60/90min 100/150/200 cm

Verification

UB III/B-06-005 • 3102/717/07 • UB 3.1/09-021 • UB III/B-08-012 • UB III/B-08-016 • UL 10 (b) (2009) • UL 10 (c) (2009) • UL 10 (d) (2009) • NFPA 252 (2012)

Closing direction

From top to bottom

Fire resistance

E 30 • E 60 • E 90 • EW 30 • EW 60 • classified according to DIN EN 13501-2

Closing cycles

C2

Constructive system design - System drawing

1 Smoke detector 2 Casing 3 Side guide 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release


1 Smoke detector 2 Casing 3 Side guide 4 Fixing bracket 5 Fabric 6 Closing element 7 Tubular motor 8 Control module 9 Control with operating unit 10 Manual release

Classification

Fabric

System width (SB)

drop length (AL)

t

h

E 90 / EW 30

Ecotex 1100

≥ 1.1 m -≤ 3 m

≤ 3 m

200 mm

220 mm

EW 90

Heliotex EW

≥ 1.1 m -≤ 3 m

≤ 3 m

200 mm

220 mm

Special sizes on request - technically feasible up to a width of 7m (Ecotec 1100) or 6m (Heliotex)

Closing strips

Standard

Standard

Special

Spring-loaded closing strip

 - Spring-loaded closing strip

Type Special

Casing installation options

Wall mounting

Suspension mounting

Ceiling mounting

Guide rails

Standard

80 K

Guide rails - 80 K

a 80 mm b 60 mm

80 KB

Guide rails - 80 KB

a 80 mm b 60 mm

80 KN

Guide rails - 80 KN

a 80 mm b 60 mm aN 85 mm bN 70 mm

References

Product - Palace of Justice, Amsterdam, The Netherlands

Palace of Justice, Amsterdam, The Netherlands

Product - House of the Sea | Vienna, Austria

House of the Sea | Vienna, Austria

Product - EDGE Amsterdam West | Amsterdam, Netherlands

EDGE Amsterdam West | Amsterdam, Netherlands