Product description
In case of an alarm, self-closing smoke protection closure of textile construction or non-heat-insulating fire and smoke protection curtain in vertical installation position and closing direction.
Type |
Smoke protection closure of textile construction or non-thermally insulating fire and smoke protection closure |
Verification |
CE identification pursuant to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016 |
Closing direction |
From top to bottom |
Fire resistance |
E 0 – EW 120 • tested in compliance with EN 1634-1:2014+A1:2018 • Classified according to EN 13501-2:2016 |
Smoke protection |
Classified according to EN 13501-2:2016 |
Closing cycles |
C0, C, C1, C2 • tested in compliance with EN 12605:2000-08 and EN 12604:2017-12 • Classified according to EN 13501-2:2016 |
Fire behaviour of textile |
A2-s1, d0; B-s1, d0; E-d2 • tested in compliance with ISO 1716 and EN 13823 or ISO 11295-2 • Classified according to EN 13501- 1:2018 |
Environmental conditions |
Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.). |
Visible surfaces |
Galvanised, RAL and NCS standard colours |
Downloads
1 Smoke detector 2 Housing 3 Guide rail 4 Control module 5 Trigger device q Clear shell construction height x Clear shell construction width s System height r Clear system height y Clear system width z System width t Depth h Height v Offset a Width b Depth c Cover
Classification |
Size max.** |
Fabric |
Wall thickness* |
Housing |
Guide rails |
---|---|---|---|---|---|
E 120 |
8792 x 5000 |
Heliotex |
175 |
Typ B, C, D, E |
Typ 1, 2 |
EW 90 |
8792 x 6000 |
Heliotex |
150 |
Typ B, C, D, E |
Typ 1, 2 |
EW 120 |
4340 x 2700 |
Heliotex |
175 |
Typ B, C, D, E |
Typ 1, 2 |
C2 |
7500 x 5000 |
Heliotex |
|||
Sa*** |
103,6 m |
Protex 600 2S |
150 |
Typ B, C, D, E |
Typ 1, 2 |
Sa*** |
117,2 m |
Protex 1100 2S |
150 |
Typ B, C, D, E |
Typ 1, 2 |
Sa*** |
76,8 m |
Heliotex |
150 |
Typ B, C, D, E |
Typ 1, 2 |
S200 |
Area 25,2 m2 |
Protex 600 2S |
* * The installation situation must comply with the building code requirements of the country of installation. The fire resistance of a ceiling or wall support structure and the adjoining The fire resistance of a ceiling or wall support structure and of the adjacent components must at least correspond to that of the fire and / or smoke protection closure, fire and / or smoke protection curtain. Evidence of the stability and serviceability of the adjacent walls and components must be provided under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN1366-7:2004 and EN1363-1:2020. The fire protection system must not be subjected to any additional loads other than its own weight, even in the event of a fire. apart from its own weight. ** Larger dimensions on request *** Joint length (normative: 3-sided without end strip) must not be exceeded. **** The area and the joint length (normative: 4-sided) must not be exceeded.
Casing installation options
References