FIBERSHIELD®-E
Product description
High degree of standardisation and thus economical shielding system with "Gravigen" drive system, i.e. closing without external energy, so that no fire-resistant cables are required.
10.000 motor cycles are possible. Different classifications achievable through different fabric types. Large fire protection curtain systems at least class C 2.
Equipment options: Safety contact strip, spring-loaded closing strip.
Type | Textile fire protection curtain |
Achievable protection goals | EI - with fire load free zone | EI - with sprinklers |
Fabric | Heliotex | Ecotex 1100 A2 |
Fire load free zone | Heliotex: EI 30/60/90min 20/30/50 cm | Protex/Ecotex: EI 30/60/90min 100/150/200 cm |
Verification | UB III/B-06-005 | 3102/717/07 | UB 3.1/09-021 | UB III/B-08-012 | UB III/B-08-016 |
Closing direction | From top to bottom |
Fire resistance | E 30 | E 60 | E 90 | EW 30 | EW 60 | classified according to DIN EN 13501-2 |
Closing cycles | C2 |
Legend System components:
1 = Smoke detector
2 = Casing
3 = Side guide
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release
Structural system design (system drawing)
Classification | Fabric | System width (SB) | Drop length (AL) | t (mm) | h (mm) |
E90 / EW 30 | Ecotex 1100 | ≥ 1,1 m - ≤ 3 m | ≤ 3 m | 200 | 220 |
EW 90 | Heliotex EW | ≥ 1,1 m - ≤ 3 m | ≤ 3 m | 200 | 220 |
Special sizes on request - technically feasible up to a width of 7m (Ecotec 1100) or 6m (Heliotex)
Closing strips
Standard
Spring-loaded closing strip
Typ = Sonder
Casing installation options
Wall mounting
Suspension mounting
Ceiling mounting
Guide rails
80 K
a = 80 mm
b = 60 mm
80 KB
a = 80 mm
b = 60 mm
80 KN
a = 80 mm
b = 60 mm
aN = 85 mm
bN = 70 mm